Sunsynk Fault Codes

Inverters

Description

DC input polarity reverse fault

On-grid - Three Phase

Check the PV input polarity.

Description

DC insulation impedance permanent fault

On-grid - Three Phase

Check the grounding cable of inverter.

Description

DC leakage current fault

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

Ground fault GFDI

On-grid - Three Phase

Check the solar panel output connection.

Description

Read the memory error

On-grid - Three Phase

Failure in reading memory (EEPROM). Restart the inverter if
the fault still exists, contact your installer or Sunsynk service.

Description

Write the memory error

On-grid - Three Phase

Failure in writing memory (EEPROM). Restart the inverter if
the fault still exists, contact your installer or Sunsynk service.

Description

GFDI blown fuse

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

GFDI grounding touch failure

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

IGBT damaged by excessive drop voltage

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

Auxiliary switch power supply failure

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC main contactor errors

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC auxiliary contactor errors

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

Working mode changed/Grid
mode changed

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

DC firmware over current

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC firmware over current

On-grid - Three Phase

1. The internal AC sensor or detection circuit on control
board or connection wire may loose.
2. Restart the inverter, if the error still exists, please contact your installer or Sunsynk service.

Description

GFCI(RCD) Ac leakage current fault

On-grid - Three Phase

1. This fault means the average leakage current is over
300mA. Check whether DC power supply or solar panels
is ok, then check ‘Test data’-> ‘diL’ value is about 120;
Then check the leakage current sensor or circuit( the following picture). Checking test data needs using big LCD.
2. Restart the inverter, if the error still exists, please contact your installer or Sunsynk service.

Description

Three phase current, over-current
fault

On-grid - Three Phase

Hardly appear the code. Never ever happened so far

Description

AC over current fault of hardware

On-grid - Three Phase

1. Check AC sensor or detection circuit on control board or
connection wire.
2. Restart the inverter or factory reset, if the error still exists, please contact your installer or Sunsynk service.

Description

All hardware failure synthesis

On-grid - Three Phase

1. When inverter is running, wifi plug plugin,will occur F19.
2. Restart the inverter or factory reset, if the error still exists, please contact your installer or Sunsynk service.

Description

DC over current fault of the hardware

On-grid - Three Phase

Not available

Description

DC leakage flow fault

On-grid - Three Phase

Hardly appear the code. Never ever happened so far

Description

Crash stop (if there is a stop button)

On-grid - Three Phase

Contact your installer for help

Description

AC leakage current is transient
over current

On-grid - Three Phase

1. This fault means the leakage current is above 30mA
suddenly. Check whether DC power supply or solar
panels is ok, then check ‘Test data’-> ‘diL’value is about
120; Then check the leakage current sensor or circuit.
Check test data needs using big LCD.
2. Restart the inverter, if the fault still exists, contact your
installer or Sunsynk service.

Description

DC insulation impedance failure

On-grid - Three Phase

1. Check Vpe resistance on main board or detection on
control board. Check PV panels is OK. Many times this
issue is the PV problem.
2. Check whether the PV panel (aluminum frame) is grounded well and inverter is grounded well. Open the cover of
inverter and then check the inside ground cable is fixed
well on the shell.
3. Check if the AC/DC cable, terminal block are shorted to
ground or the insulation is damaged.
4. Restart the inverter, if the fault still exists, contact your
installer or Sunsynk service.

Description

DC feedback fault

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

The DC busbar is unbalanced

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

DC end insulation error

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

Inverter 1 DC high fault

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC load switch failure

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC main contactor failure

On-grid - Three Phase

1. Check relays and AC voltage of relays.
2. Check relays driver circuit.
3. Check if the software is not suitable for this inverter. (Old
inverter not have relays detection function)
4. Restart the inverter, if the fault still exists, contact your
installer or Sunsynk service.

Description

DC boost soft start

On-grid - Three Phase

Not available.

Description

Inverter 2 DC high fault

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC over current

On-grid - Three Phase

AC current sensor or its circuit have issue. Check if the inverter type is not right.

Description

AC current over load

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

No AC grid

On-grid - Three Phase

1. Check AC grid voltage. Check AC voltage detection circuit. Check if the AC connector in good condition. Check
whether the AC grid is normal in voltage.
2. Restart the inverter, if the fault still exists, contact your
installer or Sunsynk service.

Description

AC grid phase error

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC three-phase voltage unbalance
failure

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC three-phase current unbalance
failure

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC over current(one cycle)

On-grid - Three Phase

1. Check AC current sensor and its circuit.
2. Restart the inverter, if the fault still exists, contact your
installer or Sunsynk service.

Description

DC over current

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC Line W,U over voltage

On-grid - Three Phase

Check the AC voltage protection setting. And Check if the AC
cable is too thin. Check the voltage difference between LCD
and meter.

Description

AC Line W,U low voltage

On-grid - Three Phase

Check the AC voltage protection setting. Check the voltage
difference between LCD and meter. Also need to check
whether AC cables are all firmly and correctly connected.

Description

AC Line V,W over voltage

On-grid - Three Phase

Not available.

Description

AC Line V,W low voltage

On-grid - Three Phase

Not available.

Description

AC Line U,V over voltage

On-grid - Three Phase

Not available.

Description

AC Line U,V low voltage

On-grid - Three Phase

Not available.

Description

AC Over frequency

On-grid - Three Phase

Check the frequency protection setting.

Description

AC lower frequency

On-grid - Three Phase

Check the frequency protection setting.

Description

U phase grid current DC component over current

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

V phase grid current DC component over current

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

W phase grid current DC component over current

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC inductor A, phase current
DC current high

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC inductor B, phase current
DC current high

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC inductor C, phase current
DC current high

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

DC busbar voltage is too high

On-grid - Three Phase

1. Check PV voltage and Ubus voltage and its detection
circuit. If the PV input voltage exceeds the limit, please
reduce the number of solar panels in series.
2. For Ubus voltage, please check the LCD display.

Description

DC busbar voltage is too low

On-grid - Three Phase

1. It tells the PV input voltage is low and it always happens
in the early morning.
2. Check PV voltage and Ubus voltage. When inverter is
running, then showing F56, maybe Loss of driver or
need update firmware.
3. Restart the inverter, if the fault still exists, contact your
installer or Sunsynk service.

Description

AC reverse irrigation.

On-grid - Three Phase

AC reverse irrigation.

Description

AC grid U over current

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC grid V over current

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

AC grid W over current

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

Reactor A phase over current

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

Reactor B phase over current

On-grid - Three Phase

Hardly appear the code. Never ever happened so far.

Description

ARC fault

On-grid - Three Phase

1. Check PV module cable connection and clear the fault;
2. Seek help from us, if can not go back to normal state.

Description

IGBT heat sink high temperature

On-grid - Three Phase

1. Check temperature sensor. Check if firmware is suitable
for the hardware. Check if the inverter is its right model.
2. Restart the inverter, if the fault still exists, contact your
installer or Sunsynk service.